ModiconTypedAddr1Offset
Applies the offset for "Type specified" Modbus addresses. For example, the IC0025 device should be 1-based.
May be set in a parent context tag if you have Modbus devices with differing address offsets.
"Type specified" means addresses such as the HC1 and IR2 format. This does not apply to addresses written as numbers only. (For example, 40001 is always the first address in the 40000 block, and is equivalent to HR1 when ModiconTypedAddr1Offset is 0, or HR0 when ModiconTypedAddr1Offset is 1)
Section: System
Default: ModiconTypedAddr1Offset = 1
*Restart Required (Settings.Startup property)