CallOutPriority

Controls whether the Alarm Notification System should contact operators when alarms have gone unacknowledged for a user-defined period of time. CallOutPriority variable selects the priority of alarms what will be sent by the VTScada Alarm Notification System.

 

If set to 0, the Alarm Notification System is disabled.

If set to 1, the Alarm Notification System will notify designated operators of only those alarms that have a priority of 1 (critical).

If set to 2, the Alarm Notification System will notify designated operators of only those alarms that have a priority of 1 (critical), or 2 (urgent).

 

Related property: MaxCallAlarmPriorityReported

 

Section:  System

Default: CallOutPriority = 2

*No restart required (Settings.Dynamic property)